AW-Lake Clamp-On Ultrasonic Transit Time Flow Meter

, ,

AW-Lake Clamp-On Ultrasonic Transit Time Flow Meter

The AW-Lake Clamp-On Ultrasonic Transit Time Flow Meter fastens on the outside of vertical or horizontal pipes ranging in size from ½” through 48”. Housed in a water-and dust-tight NEMA4X polycarbonate enclosure, the Clamp-On Ultrasonic Flow Meters are compatible with a range of metal and plastic pipe materials and corrosive liquids that would damage standard flow meters. As a result, the non-intrusive, clamp-on ultrasonic sensors feature enhanced flow measurement with no pressure drop in a range of applications such as food or chemical processing plants, oil refineries, and more.

SKU: sku315 Categories: , ,

Product Specs
Accuracy
±1.0% of reading from 1.5 to 40 ft/sec (0.5 to 12.0 m/sec) and ±0.015 ft/sec (±0.0046 m/sec) for velocity below 1.5 ft/sec (0.46 m/sec)
Repeatability
±0.25%
Flow Measuring Range
±0.07-40 ft/sec (±0.02-12 m/sec)
Operating Temperature Range
Electronics:-5°F to 140°F (-20 to 60°C)
Transducer:-40°F to 300°F (-40 to 150°C)
Pipe Diameter
SE16A: 0.5″ -1.5″ (15 mm -40 mm)
SE16B: 2″ -10″ (50 mm -250 mm)
SE16C: 12″ -48″ (300 mm -1200 mm)
Materials
Brass
Carbon Steel
Stainless Steel
Aluminum
Cast Iron
Concrete Lined Ductile Iron
Copper
Ductile Iron
Fiberglass
HDPE
Pipes with bonded liners including Epoxy, Rubber, and PTE
PVC
PVDF
Operating Frequency
SE16A: 2.56 MHz
SE16B: 1.28 MHz
SE16C: 640 kHz
Power Input
100-240 VAC / 50-60 Hz, 10 VA max
Optional: 9 -32 VDC, 10 Watts max
Analog Output
1,000 ohm load max
Isolated 4-20mA/0-5V
Programmable Offset
Control Relays
2 Relays: form C dry contacts rated 5 amp SPDT; programmable flow alarm and/or flow proportional pulse
Optional: 4 additional (6 total), rated 5 amp SPDT