Electroswitch Arga Series 1000 Utility Substation Battery Monitor, Panel Mount, Rack Mount, and Portable

, ,

Electroswitch Arga Series 1000 Utility Substation Battery Monitor, Panel Mount, Rack Mount, and Portable

The Electroswitch Arga Series 1000 Utility Substation Battery Monitor is a breakthrough in battery monitoring, and ground fault detection. This highly accurate instrument is powered by the same battery it monitors. It displays battery bus voltage, ripple voltage, ripple current (with an optional clamp-on sensor 25-1100-H1) +Bus voltage to GND,-Bus voltage to GND faults, and high impedance faults based on ripple voltage and ripple current. Mounting options for the Series 1000 Arga Battery Monitor include panel mount, or 19″ rack mount (3U or 4U), and portable for single or dual units. These battery monitors have ground fault locator, and corrosion detection options available.

Product Specs
Operating Temp
-4°F to 131°F (-20°C) to 55°C)
Mounting
Panel
Portable
Rack
Contact Rating
28VDC, 25mA at 150VDC
2A at 120VAC
Input Voltages
125VDC
24VDC
250VDC
48VDC
Voltage Indication
0 to 199.9VDC
Voltage Accuracy
±0.2VDC
Display Ranges
+Bus to Ground (+ to GND)
Battery Voltage (BAT)
Bus to Ground (-to GND)
Ground Fault Voltage (Fault)
Battery Input
100-360VDC, 5VA (for 250 V battery)
36-72VDC, 3VA (for 48 V battery)
50-180VDC, 3VA (for 125 V battery)
Ground Resistors
15 KΩ ±1% from each bus to ground (for 48 V battery)
30.83 KΩ ±1% from each bus to ground (for 125 V battery)
60.50 KΩ ±1% from each bus to ground (for 250 V battery)
Standard Outputs
Analog: 4~20mA
Digital: DNP3, Modbus